M65 FeaturesTechnical SpecificationsStandard and Optional EquipmentInstallation Dimensions
Engine speed rev/min Type of Operation Typical Generator Output Nett Engine Power
kVA kWe kWm bhp
1500 Prime Power Standby Power 77.1
85.0
61.7
68.0
68.5
75.5
91.8
101.2
1800 Prime Power Standby Power 90.6
99.6
72.5
79.7
80.5
88.5
107.9
118.6

Note: All engine rating data based on operation under BS551d:1996, ISO 3046/1: l995 and DIN 6271 conditions

FUEL CONSUMPTION
Power Rating % 1500 rev/min 1800 rev/min
litres/hr UK gal/hr litres/hr UK gal/hr
110 19.2 4.2 26.6 5.85
100 17.1 3.8 19.9 4.4
75 12.9 2.8 15.9 3.5
50 9.6 2.1 10.9 2.4
TEST CONDITIONS
  • Air temperature 25° C (80.6°F), barometric pressure 100 kPa (29.5 in Hg), relative humidity 30%, maximum exhaust back pressure 5 kPa, maximum inlet restriction l kPa.
    For operation outside of these conditions please consult your Perkins contact.
    Performance tolerance quoted by Perkins is ± 5% 
    Electrical ratings assume a power factor of 0.8 and a generator efficiency of 90%
RATING DEFINITIONS
  • Prime power
    Power available at variable load in lieu of main power network. An overload of 10% is permitted for one hour in every twelve hours of operation
  • Standby power
    Power available at variable load in the event of a main power network failure. No overload is permitted